Türkçe  English
 

BASINÇLI KAPLAR SAN. A.Ş.

NEWS

Powdered and Water Based Fire Extinguishers

SPECIFICATIONS

  • Each one of the dry powdered and water based portable permanent pressure extinguishers are ;
    1. Produced from welded steel sheets.
    2. Tested at 25 bar hydrostatic pressure and leak proofed.
    3. Primed by surface cleaning with shot blasting and protected against corrosion.
    4. Coated with electrostatic painting .
    5. Dry chemical powdered extinguishers are effective for the following fires ; class A (wood, coal, paper, textile products, etc.). class B (petrol, oil, alcohol,etc.) , class C (hydrogen, Pg. acetylene, etc.) and class D (light metals, aluminium ; magnesium, etc.)
    6. Water based extinguishers are effective for the following fires ; class A (wood, coal, paper, textile products, etc.) and class B (petrol, oil, alcohol,etc.) 
  • Powdered extinguishers are filled with extremely fine (25-30 microns) chemical powder which has a superior extinguishing performance.
  • These extinguishers contain special trigger apperature. manometer and safety accessories which can be used easily.
  • The manufacturer reserves the right to alter specifications at it's discretion.

 

 

 

PORTABLE

WITH TROLLEYS

Type

 

KT
A(S)01

KT
A(S)02

KT
A(S)06

KT
A(S)12

KT
A(T)06

KT
A(T)12

KT
A(S)25

KT
A(S)50

KT
A(T)25

KT
A(T)50

KT
A(T)250

Capacity

Kg.

1

2

6

12

6

12

25

50

25

50

250

Cartridge

Lt.

-

-

-

-

0,22

0,47

-

-

3

4

26,7

Body Material

 

Steel
Sheet

Steel
Sheet

Steel
Sheet

Steel
Sheet

Steel
Sheet

Steel
Sheet

Steel
Sheet

Steel
Sheet

Steel
Sheet

Steel
Sheet

Steel
Sheet

Diameter  ( Ø )

mm

89

110

150

189

150

189

245

245

300

300

650

Height (~)

mm

320

380

540

625

480

550

1000

1120

1000

1120

1770

Test Pressure (min)

Bar

25

25

25

25

25

25

25

25

25

25

35

Working pressure (min)

Bar

17

17

17

17

17

17

17

17

17

17

17

Working Temperature

°C

-20,+60

-20,+60

-20,+60

-20,+60

-20,+60

-20,+60

-20,+60

-20,+60

-20,+60

-20,+60

-20,+60

Full Weight (~)

Kg.

2.7

4.5

10.5

18.5

10.5

19.5

46,5

87

49,5

98

500

Range of discharge (min)

m

2.5

3

6

7

6

7

6

7

6

7

7

Discharge Time (min)

sn

6

7

9

15

9

15

15

30

15

30

150

Effective Fire Class

 

ABC

ABC

ABC

ABC

ABC

ABC

ABC

ABC

ABC

ABC

ABC

 

 

 

PORTABLE

WITH TROLLEYS

Type

 

FM-(S)02
FOAM

FM-(S)06
FOAM

WT-(S)06
WATER

WT-(S)50
WATER

FM-(S)50
FOAM

FM-(T)50
FOAM

FM-(T)250
FOAM

Capacity

Lt.

2

6

6

50

50

50

250

Cartridge

Lt.

-

-

-

-

-

4

26,7

Body Material

 

Sheet Steel

Sheet Steel

Sheet Steel

Sheet Steel

Sheet Steel

Sheet Steel

Sheet Steel

Diameter  ( Ø )

mm

110

150

150

245

245

300

650

Height (~)

mm

380

540

540

1120

1120

1120

1770

Test Pressure (min)

Bar

25

25

25

25

25

25

35

Working pressure (min)

Bar

17

17

17

17

17

17

17

Working Temperature

°C

0,+60

0,+60

+5,+60

+5,+60

0,+60

0,+60

0,+60

Full Weight (~)

Kg.

4.5

10.5

10.5

87

87

98

500

Range of discharge (min)

m

2

3

3

5

5

5

5

Discharge Time (min)

sn

6

9

9

30

30

30

150

Effective Fire Class

 

BC

BC

A

A

BC

BC

BC